The maintenance factor required for determining initial illuminance which describes the installation’s operating behaviour must be agreed upon by designer and operator of the lighting installation according to EN 12464-1. Where this is not possible, the following reference maintenance factors are to be used for planning:
0,8 for short periods of use or low degrees of soiling in relation to cleanliness requirements in healthcare rooms, or
0,67 for normal periods of use or high degrees of soiling in relation to cleanliness requirements in healthcare rooms.